Ventilation Rate Procedure for HVAC Systems in the Healing Environment

Ventilation Rate IAQ Procedure - Air MeasuringThe IBC/IMC, the AIA, and Chapter 7 of the ASHRAE Handbook—HVAC Applications all reference ANSI / ASHRAE Standard 62 for determining ventilation. ANSI / ASHRAE Standard 62 provides two methods for engineers to follow to determine the required minimum ventilation rate to achieve acceptable indoor air quality.

To obtain compliance for ventilation design, there are two procedures in the ASHRAE standard. The ventilation rate procedure states that acceptable IAQ is achieved by providing ventilation air of the specified quality and quantity to the space. The indoor air quality procedure identifies a method for achieving acceptable IAQ within the space by controlling known and specifiable contaminants.

Ventilation Rate Procedure

The ventilation rate procedure provides a more definitive, prescriptive procedure based on physiological needs and subjective evaluations. The indoor air quality procedure uses guidelines for the specification of acceptable concentrations of certain contaminants in indoor air —with no prescriptive formula for ventilation rates.

The Indoor Air Quality (IAQ) Procedure

The indoor air quality procedure typically does not result in lower outside air in healing environment applications since the various potential sources of contamination require ventilation rates to be equal to that of the ventilation rate procedure. Additionally, the indoor air quality procedure requires the designer to specifically identify how each of the known contaminants is to be dealt with. The problem facing system designers with this procedure is in determining the possible contaminants that may result from the eventual use/occupancy of the healing environment. For example, controlling formaldehydes, aldehydes, nitrogen dioxides, organics, etc., all need to be understood and accomplished with “engineering reason” when tackling this method. As a result, most designers opt for the more common ventilation rate procedure (VRP ) to determine outdoor airflow needs at the space and system levels. This method prescribes the outdoor air quality acceptable for ventilation, outdoor air treatment where necessary, ventilation rates, and the criteria for reductions of outside air where recirculation treatments occur.

ASHRAE also addressed maintenance of outside ventilation systems. ANSI /ASHRAE Standard 62-2001 identifies minimum ongoing operation and maintenance criteria. The requirements of this section apply to buildings and their ventilation systems and their components constructed or renovated. In section 8.4 of ASHRAE 62, it states:

At a minimum of once every three months or as specified in the Operations and Maintenance Manual, the outdoor air dampers and actuators shall be visually inspected or remotely monitored and determined to verify that they are functioning in accordance with the Operations and Maintenance Manual.

ANSI /ASHRAE Standard 62’s definition of a maintenance manual is as follows:

An operations and maintenance manual either written or electronic shall be developed and maintained on site or in a centrally accessible location for the working life of the applicable ventilation system equipment or components.

This manual shall be updated as necessary. The manual shall consist, at a minimum, of the operation and maintenance procedures, final design drawings, operation and maintenance schedules, and any changes made thereto and the maintenance requirements.

Measuring Air Quality

Ruskin Air Measuring Equipment

Ruskin has the most comprehensive line of air measuring and control solutions in the industry.  Products include differential pressure probes for high velocity applications, combination units that measure and maintain flow, and highly sophisticated, intelligent solutions that incorporate thermal dispersion technology with microprocessor based controls that communicate with any building automation system.

RSKN_Go_Green_Logo

For more information about Ruskin’s complete product line, application and design support, and our state-of-the-art manufacturing capabilities, contact your local Ruskin representative nearest you or Contact Ruskin directly at (816) 761-7476.

Advertisements

Leave a Reply

Fill in your details below or click an icon to log in:

WordPress.com Logo

You are commenting using your WordPress.com account. Log Out / Change )

Twitter picture

You are commenting using your Twitter account. Log Out / Change )

Facebook photo

You are commenting using your Facebook account. Log Out / Change )

Google+ photo

You are commenting using your Google+ account. Log Out / Change )

Connecting to %s