Miami-Dade County Approval Tests for Louvers

Louver Building Miami DadeThe South Florida Building Code (SFBC) states that products installed on the exterior of buildings must be designed to withstand the severe conditions produced by hurricanes. However, the widespread failure of various building products during Hurricane Andrew in 1992 identified a need for stronger code enforcement. Recognizing that standardized testing and product control could assist enforcement, the Metro-Dade County (later changed to include all of Miami-Dade County) Florida Building Code Compliance Office (BCCO) developed a series of test protocols that subject products to the rigors of hurricane wind and rain conditions.

Miami DadeTo gain Miami-Dade County Approval, louvers may be required to pass as many as four different tests — three are structural and one measures wind driven rain penetration resistance. These tests are referred to as PA’s or Protocol and Application Standards.

PA-100(A): Wind Driven Rain Penetration Test

The Building Code Compliance Office (BCCO) requires this test if the room the louver is installed in is designed to be dry (room is not designed to drain water and/or houses items that are not water resistant). This test subjects the louver to high velocity winds and heavy simulated rainfall. Using a wind generator and water jets that inject the equivalent to 8.8″ per hour rainfall into the airstream, 15 minute tests are run at wind velocities of 35, 70, and 90 mph. The final 110 mph test is performed for 5 minutes. The louver must allow no water penetration at 35 and 70 mph, and only .05% penetration at 90 and 110 mph.

PA-202: Uniform Static Air Pressure Test

If a louver is installed in a room that can drain water and houses water resistant items, the wind driven rain test is not required. Instead, the PA-202 test is performed. In this procedure, the louver is installed in a chamber and uniform static air pressure is applied in positive and negative directions. Several pressure levels are applied in increasing magnitude until a load equal to 1.5 times the design windload is attained. Pressures are sustained for 30 seconds. The deflection of blades, frames and supports is measured during the test and the amount of recovery is checked afterwards. Throughout the test the anchorage system is also monitored for failure. Design windloads for hurricane applications can produce static pressures in excess of 28″ w.g. If the room is considered a closed structure that cannot withstand this pressure or if it houses equipment that cannot handle the pressure, the BCCO code requires the louver/damper assembly be subjected to the PA-201 and PA-203 tests.

PA-201: Large Missile Impact Test

Impact on Miami Dade LouverThis test simulates wind-driven debris that is often present in hurricanes. In the test, the louver assembly is impacted with a 2″x 4″ board weighing 9 lbs. and traveling at approximately 34 mph. At least three separate impacts are conducted and the louver must prevent the board from both penetrating the assembly or creating a significant opening.

PA-203: Cyclic Wind Pressure

This test is conducted only after the Missile Impact Test has been done. By simulating the forces applied to a louver by repeated severe wind gusts, this test exposes possible weaknesses in the assembly created by the missile impacts. In this test, the louver assembly is installed in a chamber similar to the Uniform Pressure test. However, the pressures are applied for only a few seconds and repeated several hundred times. Pressure is increased until 1.3 times the design windload is achieved. As in the PA-202 procedure, the deflection of the components and the anchorage system are examined.

Miami Dade Louver Cross SectionRuskin’s Hurricane Louvers

Ruskin’s Hurricane Louvers are designed to exceed impact resistance and windload requirements with predesigned proven installation methods. Ruskin was the first manufacturer to gain Miami-Dade County approval for louvers. These louvers are built to withstand up to 160 psf on some products based upon the criteria in TAS 201, 202 and 203 as well as AMCA 540/550.

Hurricane Louver Products

For more information about Ruskin’s complete product line, application and design support, and our state-of-the-art manufacturing capabilities, contact your local Ruskin representative nearest you or Contact Ruskin directly at (816) 761-7476.

Advertisements

Leave a Reply

Fill in your details below or click an icon to log in:

WordPress.com Logo

You are commenting using your WordPress.com account. Log Out / Change )

Twitter picture

You are commenting using your Twitter account. Log Out / Change )

Facebook photo

You are commenting using your Facebook account. Log Out / Change )

Google+ photo

You are commenting using your Google+ account. Log Out / Change )

Connecting to %s