Ducted or non ducted air systems

Designing High Performance Duct Systems

Introduction

Ducted or non ducted air systemsFor the past 50+ years, engineers have been “designing” duct systems. Quite often, they were not actually designing the duct system, but were sizing duct the duct according to some rules of thumbs. The rules of thumbs varied by different engineering firms and often ducts were sized to be round by a predetermined friction rate that was chosen by the engineering firm. Then if the round duct did not fit and sometimes when it does, it’s often converted to rectangular, making it a lot less efficient system. Often, the whole ductwork system is “sized” that way using a Ductulator. Not much thought is given to the fittings used and often leakage of the system is not considered during the design phase.

Duct Design General Concepts

So how do we go about designing duct system to be green? There are many aspects to design, but focusing on the duct system design we want a system that minimizes the use of energy, time and material and make sure it meets the acoustical requirement of the application. To accomplish these goals we have to consider what the duct system will be used for (standard air conditioning, exhaust, or other), duct system layout, fitting selection, system leakage, acoustical properties and equipment selection.

There are three common methods of duct sizing or design for commercial and industrial duct systems: equal friction, static regain and constant velocity. Both the supply side (positive pressure) of the fan or air-handling unit (AHU) and the return side and makeup air side (negative pressure) of the fan have to be considered. The equal friction method and constant velocity systems can be used for either the supply or return side. Most often equal friction is used on the supply and the return systems while constant velocity is used for exhaust systems that have to convey particulate or fumes. Static regain however is strictly used for a positive pressure design.

This article will focus on the design of the duct system on the positive side of the fan or Air Handling Unit (AHU). Other important aspects that that should be looked at during the design phase may include fan or AHU selection, system effects, leakage, diversity, room air distribution, equipment layout and commissioning. Those are topics for other papers.

spiral duct

 

Choosing a Duct Design Method

When we design duct systems we want the design method that minimizes energy, material and time. But first to dispel a myth, static regain does not automatically design systems at a lower total pressure. Any design method can be used to design a duct system for almost any pressure. A 6-in wg system can be designed either by Equal Friction (just increase the design friction rate) or by Static Regain (just increase the initial velocity). In either case though the velocities should be kept within acceptable limits to avoid noise problems. But a static regain design goal is to produce a balanced system. That is, one in which all paths are design legs, or require the exact same amount of static pressure for the legs respective airflow. For final balancing of systems, smaller sizes in non-critical paths will use excess pressures. So if two designs of the same system are created that have the same operating pressure, one with equal friction and one with static regain, the static regain method should use smaller duct sizes, because it is balancing the system. When this is the case you will likely have the benefit of more round sizes and because smaller sizes in general are used for balancing the non-design paths, the benefit of lower duct and fitting cost as well. A benefit of round duct is it has lower breakout noise, resulting in a quieter design. Another benefit is that round duct and the resultant smaller sizes are easier to install and seal. Some pros and cons of the two design methods are shown below:

Table1--

 

Total Pressure Design

Whether a system is designed with Equal Friction or with Static Regain, there is still likely to be imbalance. There should be less with the Static Regain design, but because in the real world we don’t have an infinite number of duct sizes, there is always some imbalance. Using the Static Regain design though helps to minimize this imbalance. Ideally we want all paths to be critical paths. That would mean the system is perfectly balanced. With imbalance means some paths will have more pressure (excess) available than they need, which means they likely have sections that can be made even smaller. Note to designers less efficient fittings will generate more noise, but that is generally not a problems till you get close to the final runouts. It’s best to design with high quality fittings that have lower pressure drop, then use smaller sizes. Using multiple runs of round rather than rectangular or flat oval duct could save even more money on the job. The process of taking a given design, determining the excess pressures available in the non-design legs, and making them smaller to use up the excess pressure, is often referred to as a total pressure design. It can be applied to any design method, but is most suited to be applied to the Static Regain Design method since it should already be fairly balanced. The good news is some of the duct design programs pinpoint the critical legs making it easy to identify where there will be excess pressure.

Example of Using Equal Friction vs Static Regain vs Total Pressure Design

In an article published by the Air Conditioning, Heating and Refrigeration News in their June 18 1990 edition, a system was designed with the Equal Friction sizing method with three different friction rates (0.05 in wg/100 ft., 0.10 in wg/100 ft. and 0.50 in wg/100 ft.). Then each of these three systems was designed with Static Regain, then the Total Pressure design. The system design airflow is 26,800 cfm and the designs were such that the Static Regain and Total Pressure methods had about the same operating pressure as the respective Equal Friction designs. The first section was the same size in all design methods. The results of the three designs are given in the Table 2:

Table2--

The system had a 12-inch height restriction. For the 0.05 in wg/100 ft Equal Friction design, the percent of sections that became round went from 32% to 61% by using the Static Regain design method and 71% for the Total Pressure design. Similar results can be seen for the two higher pressure designs as well.

Round ductwork cost much less than rectangular or flat oval, saves installation time, is easier to seal and the Static Regain and Total Pressure design methods are much more balanced!

The other advantage of total pressure design is that since it is a balanced system using smaller sections of duct which have higher attenuation and insertion losses. So using that knowledge, and keeping the velocities reasonable, total pressure designs should not require as much noise control.

Leakage

A high performance duct design should minimizing leakage. ASHRAE recommends the system leakage be no more than 5 percent of the total airflow volume. Why is that so important? If a system leaks and airflow requirements are not met in the locations they were intended, the leaks either have to be sealed or the fan speed must be increased to generate more volume. If the leaks are not sealed, a practice which is no longer allowed by many codes, that additional volume will need to be pushed through with a higher static, because remember that the system will continue to leak and that the airflow volume, plus the additional leakage airflow volume caused by higher static pressures will need to be overcome as well. Essentially you are changing the system curve from what was designed to what is actually happening.

The design point for a fan is where the system curve crosses the fan curve as shown in Figure 1. It assumes no leakage is occurring. If there is 10% system leakage, the duct system is essentially relieved and the system curve moves down. That is because the same volume of air does not have to move through the entire system as some has leaked out. The airflow increases while the Fan TP decreases as shown in Figure 2. We can’t just speed up the fan as shown in Figure 3 so it produces the same original Fan TP as leakage is still occurring. We will actually have to move to a higher RPM and increase both the Fan TP and the airflow so we get the correct airflow to the outlets as shown in Figure 4.

ASHRAE studies have shown the cost of leakage could be $0.00050 per cfm-hr. So a 50,000 cfm system operating 2600 hrs per year with 10% leakage of 5000 cfm, could cost an additional $6500 per year.

 FIGURE1  FIGURE2
 FIGURE3  FIGURE4

Summary

To design high performance duct systems that do not have acoustic sound problems we need to

  • minimizes the use of energy
  • minimizes the use of construction/manufacturing labor and material
  • make sure it does not contribute noise to the environment
  • design balanced systems

To best meet these objects, the Static Regain/Total Pressure design should be used to determine the duct sizes in a system. To use the Static Regain method, you have to choose an initial velocity. It is recommended you use the follow chart published in the ASHRAE Applications Handbook 2011, Table 8, page 48.14.

Table3

 

Then use Static Regain to size the duct sections, utilizing the most efficient fittings. When finished designing, use the Total Pressure design to further balance the system using smaller sizes and less efficient fittings in non-critical paths.

The final result will be a well-balanced system using the smallest sizes possible for the initial velocity. Smaller duct sizes mean:

  • more of the duct sizes will be round
  • round spiral duct is much easier to install and has fewer joints
  • many sizes will be smaller than those in other design methods, making even them easier to install and use less materials
  • smaller sizes will be easier and less costly to seal making very low leakage duct systems possible
  • the duct system will be balanced assuring everyone gets enough air and the Testing and Balancing peoples time will be minimized
  • done right, round ductwork results in quieter system with less risk of noise problems

You will likely need a computer to do the proper designs, but if you do; less time, material, and energy will be expended. With the proper controls and other components, the Static Regain/Total Pressure duct system designs are used in true High Performance Air Systems. What more could you ask for in a duct design.

Guest Blog Writer:

Pat Brooks, General Manager

esm

www.easternsheetmetal.com

Advertisements

High Performance Air Systems – In Conclusion

building envelopesToday’s tight building envelops with high occupant density and internal loads require year-round cooling in interior zones.  High performance air systems offer free cooling from airside economizers at lower outside temperatures, while VRF systems must run the compressors at all outdoor air [latent too]conditions to satisfy cooling demand.  VRF proponents often talk about energy-recovery.  However, that requires simultaneous compressor-heating and compressor-cooling operation (compression cycle).  Contrast this to a modern airside economizer used with HPAS.  Additionally, HPAS offers further part load energy saving measures using advanced control technologies which include ventilation optimization based on fresh air demand by zone, comparative enthalpy economizers with remote indication, supply air temperature reset tied to measured system demand and optimum start/stop.

As with VRF, HPAS are also available with variable compressors and fans.  This combined with the refrigeration/heating energy saving options not available with VRF save even more energy. These options include the ability to provide lower cost, and efficient gas heating systems, trending and automated reporting of total system diagnostics, user-specific building automation control strategies, measurement and control of airflow, thermal energy storage in the building structure (pre-cooling with economizer-flush at night) can reduce peak demand and shift the cooling load to times of cooler OA.

The most publicized comparison of energy use of between a ducted air system and a VRF system  is the ASHRAE Headquarters Building in Atlanta, GA. The building uses three separate HVAC systems: a variable refrigerant flow (VRF) system for spaces on the first floor, a ducted ground source heat pump (GSHP) system, primarily for spaces on the second floor, and a dedicated outdoor air system (DOAS), which supplies outside air to both floors.  The VRF system consumed 61% more energy than the ducted GSHP.

2012 Energy usage for GSHPs – 24,430.89 kWh (Jan – Dec)
Heating / cooling area for GSHPs – 15,558 sq. ft.
GSHP = 1.57 kWh / sq. ft.

Energy usage for VRF – 46,066.54 kWh (Jan – Dec)
Heating / cooling area for VRF – 18,226 sq. ft.
VRF = 2.53 kWh / sq. ft.

VRF consumed 61% higher annual kWh/sq. ft. in 2012
(2.53-1.57)/1.57* 100 = 61%

ASHRAE 15

gas monitorRisk of refrigerant leakage in occupied spaces is a safety issue for VRF but not for high performance air systems where refrigerant is located in an equipment room, rooftop unit, or minimal line-runs. Users must be cognizant of ASHRAE 15 requirements. The space served by each zone must be large enough to disperse the entire system refrigerant charge per ANSI / ASHRAE Stds. 15 and 34 and local codes.  A maximum of 25 lbs of R-410A per 1000 cuft of room volume is allowed for non-institutional spaces. Transfer ducts between rooms may be required. ASHRAE 15 refrigerating machinery room requirements also require venting of fusible plugs. When any system contains more than 110 lbs. of refrigerant these fusible plugs must be discharged “to the atmosphere at a location not less than 15 feet above adjoining ground level and not less than 20 feet from any window, ventilation opening, or exit”

High performance air systems require no scheduled maintenance in occupied spaces. For VRF indoor unit filter replacement, coil cleaning, and visual inspection of condensate drain must be done for every indoor fan coil on a scheduled basis. Both maintenance above the ceiling, condensate pan overflow risk and refrigerant leaks can result in ceiling damage and inconvenience to occupants.

Equipment performance is certified by ASHRAE and AHRI for high performance air systems and assures owners that performance meets specified levels.   ASHRAE certified air performance covers fan efficiency grades, sound levels and ducted air system leakage. AHRI certified thermal performance covers refrigeration system efficiency.

Summary

High performance ducted air systems overcome many of the disadvantages of non-optimized ducted systems. And compared to VRF, HPAS systems provide better comfort, meet ventilation codes, have a lower initial cost, consume less energy, carry no refrigerant risk, require less maintenance and provide performance certified by AMCA, AHRI.

VRF and other non-ducted systems certainly have their application as described herein. Additionally, they make sense for many mixed-use applications.   However, when system designers have a choice, it is easy to see why ducted systems – especially HPAS ducted systems – are North America’s number one choice for comfort cooling.

RSKN_Go_Green_LogoFor more information about Ruskin’s complete product line, application and design support, and our state-of-the-art manufacturing capabilities, contact your local Ruskin representative nearest you or Contact Ruskin directly at (816) 761-7476.

High Performance Air Systems – HPAS

spiral duct High performance ducted air systems (HPAS) use the best of what ducted systems can offer, and compared to VRF, provide better comfort, meet ventilation codes, have a lower initial cost, consume less energy, carry no refrigerant risk, require less maintenance and performance is certified by AMCA, AHRI.

HPAS consists of advanced digital controls, low-leak economizers for free-cooling, spiral/oval static-regain ducting, variable air volume technology, well-placed diffusers,  high efficiency fans,  superior filtration systems, air-to-air energy recovery, and variable flow compressors.

air control damperComfort, flexibility, and efficiency remain the key objectives of office HVAC.  With high performance air systems it begins with multiple zones using temperature control which can be as small as one individual office. VRF zone size is limited by the necessity for rooms large enough to disperse the refrigerant charge of the entire system per ANSI/ASHRAE Stds. 15 and 34 and local codes.

High performance air system offers better filtration with the option for MERV-13 or better filters, or photocatalytic air cleaning compared to the residential type filters found in VRF systems. Noise can also be an issue with non-ducted systems because of the small fans in the room or above the ceiling. Regarding ventilation, ASHRAE 62 ventilation codes must be met at all times during occupied hours.  VRF systems must use a separate ducted system to provide ventilation air to each and every zone.  This coupled with the need to run refrigerant lines throughout the building drive up the first cost significantly beyond a HPAS.

From a flexibility standpoint, it is easier to move diffusers and duct take-off branches, vs. DX fan coils and refrigerant lines.

What about cost?  Typical installed costs* for various systems are summarized here 

VRF $20 to $26/sq.ft.
Chilled beam $30 to $45/sq.ft
VAV Rooftop/ High Performance Air System $15 to $20/sq.ft.
Chiller and High Performance Air system $17 to $24/sq.

spiral ductSeveral energy-reducing features distinguish high performance air systems from basic ducted systems. For lower fan energy consumption, system designers achieve the best airflow performance by selecting the fan with the lowest power (not always the lowest cost, or the smallest fan).  All AHU (air handler unit), rooftop, and fan manufacturer’s selection programs provide a variety of fan selections to meet the airflow and system pressure requirements  Further optimization comes by avoiding oversizing design loads, lowering design supply air temperature, and specifying low leak spiral/oval ducting.  Next is design of a lower pressure drop air systems using large coils, large filter banks, static-regain duct design, and aerodynamic ducts (large radius elbows and fewer transitions and joints), low pressure drop terminals and plenum returns.  Complete the fan power equation by selecting efficient motors and drives, or  efficient variable speed motors and drives for part load energy savings. A fan running at one-half the design airflow operates with one-eighth the power consumption.